Partial damp diagnostic method of oil-paper insulating bushing based on frequency domain spectroscopy

  • CHEN Xiaolin,
  • FU Xiaotao,
  • WU Qiandong,
  • ZHAO Haoxiang,
  • LI Yuan,
  • MU Haibao

DOI
https://doi.org/10.12158/j.2096-3203.2022.02.020
Journal volume & issue
Vol. 41, no. 2
pp. 149 – 155

Abstract

Read online

Partial dampness is the initial stage in the bushing damp process,so the effective diagnosis of partial dampness can avoid the further development of the damp. The partial damp diagnosis method of bushing based on the frequency domain spectroscopy (FDS) is proposed in this paper. Firstly,oil-paper insulation samples with different moisture content are prepared,and partial damped samples are formed through combination. Then the FDS characteristics are obtained. The results show that partial distribution of moisture leads to oil-paper insulation interfaces with different moisture content,and the interface relaxation polarization loss peak is introduced in the FDS curves. The greater the degree of partial dampness in the radial direction,the greater the amplitude of the loss peak,and it moves to the high frequency direction. The effectiveness of the diagnosis of partial dampness of bushing based on the characteristics of the interface relaxation polarization loss peak is verified by the simulation model of the transformer bushing. It shows that a new method for early fault warning and diagnosis of the transformer bushing is provided.

Keywords