MATEC Web of Conferences (Jan 2023)
Numerical Analysis of dew point Indirect Evaporative Cooler
Abstract
An indirect evaporative cooler that uses a Maisotsenko (M) Cycle has the potential to be a green and sustainable solution for managing a building’s cooling demand since it can attain sub-wet bulb temperature without humidification. This study presents the design and simulation analysis of a crossflow indirect evaporative cooler using the COMSOL Multiphysics software for various ambient conditions. The cooler’s performance was evaluated by varying the inlet air temperatures. The analysis was conducted using numerical simulations, and the outcomes were compared with experimental data. The simulation results demonstrated that the cooler could achieve significant temperature reductions at a minor energy consumption as compared to traditional air conditioning systems. This study delivers that this system reduces the temperature of inlet air up to 22°C as well as cooling capacity and coefficient of performance values are 3.699 kW and 27.40. Overall, the results demonstrate the potential of crossflow indirect evaporative coolers as an energy-efficient alternative to conventional air conditioning systems.