Energies (Jun 2022)

Coordinated Reactive Power Control with a Variable Shunt Reactor and an Inverter-Based Wind Power Plant

  • Seung-Ho Song,
  • Soo-Bin Kim

DOI
https://doi.org/10.3390/en15134739
Journal volume & issue
Vol. 15, no. 13
p. 4739

Abstract

Read online

Underground or submarine cables have a higher capacitance component than overhead lines, and they inject a large amount of capacitive reactive power into the system. A separate reactive power compensation device is required in order for a wind power plant (WPP) connected to the public network with a cable to meet the reactive power requirements required by the grid code. In this paper, a reactive power control using a variable shunt reactor (VSR) was proposed to satisfy the reactive power requirement required by the grid code for a WPP connected to the grid through a cable. The proposed reactive power control method compensates for the capacitive reactive power of the cable by using a VSR, and it follows the reactive power command through the reactive power control of a WPP. In the section where it is difficult to follow the WPP reactive power command only with the reactive power capacity of a WPP due to cable losses or a cable reactive power compensation error of the VSR, the reactive power control is additionally supported through the hysteresis control of the VSR. The proposed method satisfies the grid codes, and it enables fast and accurate reactive power control. The performance of the proposed method was verified through simulation using MATLAB/Simulink.

Keywords