Journal of Electrical and Electronics Engineering (Oct 2014)

Short-Circuit Calculations for a Transmission Line in the Algerian Power Network Compensated by Thyristor Controlled Voltage Regulator

  • ZELLAGUI Mohamed,
  • HASSAN Heba,
  • CHAGHI Abdelaziz

Journal volume & issue
Vol. 7, no. 2
pp. 43 – 48

Abstract

Read online

In this paper, the impact of using the Thyristor Controlled Voltage Regulator (TCVR) on short-circuit calculations is studied for a high voltage transmission line in case of a phase to earth fault in the presence of a fault resistance (RF). A 400 kV single transmission line, in the Algerian power network, is used for this study where the line is compensated by TCVR FACTS device to control the voltage and active power of the line. The impact of the fault resistance is studied to reflect its effect on short-circuit calculations including symmetrical current components, transmission line currents, voltage symmetrical components, and transmission line voltages, without and with TCVR. The obtained simulation results match the presented theoretical analysis.