E3S Web of Conferences (Jan 2020)

Oil Chromatographic Analysis and Fault Diagnosis Case Analysis for Transformers

  • Li Yanping,
  • Li Yong,
  • Li Yunqi

DOI
https://doi.org/10.1051/e3sconf/202014502067
Journal volume & issue
Vol. 145
p. 02067

Abstract

Read online

The production principle of characteristic gas in transformer oil and its corresponding transformer fault type are discussed in this paper. Aiming at the fault of multiple characteristic gases exceeding the standard in a 110 kV transformer oil, this paper analyzed the fault reasons according to the characteristic gas method and the three-ratio method, and combined with relevant tests, it was judged that the transformer core multiple grounding fault caused the fault. The on-site inspection verifies the correctness of the failure analysis results and the corresponding measures were adopted to eliminate the transformer faults.