Serbian Journal of Electrical Engineering (Jan 2013)

Detecting the single line to ground short circuit fault in the submarine’s power system using the artificial neural network

  • Behniafar Ali,
  • Darabi Ahmad,
  • Banejad Mahdi,
  • Baghayipour Mohammadreza

DOI
https://doi.org/10.2298/SJEE130601015B
Journal volume & issue
Vol. 10, no. 3
pp. 445 – 457

Abstract

Read online

The electric marine instruments are newly inserted in the trade and industry, for which the existence of an equipped and reliable power system is necessitated. One of the features of such a power system is that it cannot have an earth system causing the protection relays not to be able to detect the single line to ground short circuit fault. While on the other hand, the occurrence of another similar fault at the same time can lead to the double line fault and thereby the tripping of relays and shortening of vital loads. This in turn endangers the personals' security and causes the loss of military plans. From the above considerations, it is inferred that detecting the single line to ground fault in the marine instruments is of a special importance. In this way, this paper intends to detect the single line to ground fault in the power systems of the marine instruments using the wavelet transform and Multi-Layer Perceptron (MLP) neural network. In the numerical analysis, several different types of short circuit faults are simulated on several marine power systems and the proposed approach is applied to detect the single line to ground fault. The results are of a high quality and preciseness and perfectly demonstrate the effectiveness of the proposed approach.