Thermal modelling of oil-filled power transformer TM - 160/10
Abstract
The results of modeling the thermal characteristics of the dry and oil-filled power transformer TM-160/10 in idle and short circuit modes are presented. The electrical, geometric and thermal characteristics of the TM-160/10 transformer are determined. Computer modeling is performed in the software package ANSYS 17.1. The 2D distributions of temperature and density of heat flows in the transformer in the longitudinal and transverse sections are determined. It is shown that the use of transformer oil for cooling the transformer significantly reduces the temperatures in the active part. The temperature distribution occupies the range of 67-91 °С. Accordingly, the temperature of the most heated part is 91 °C and also corresponds to the low voltage winding. The dependence of the most heated point of the transformer on the operating mode was studied. A formula is proposed for calculating the maximum temperature of a transformer as a function of power loss.