Energies (Sep 2022)

Measurements and Modeling of Long Continuing Current in the Lightning Protection System of a Residential Building

  • Grzegorz Masłowski,
  • Sebastian Hajder

DOI
https://doi.org/10.3390/en15196862
Journal volume & issue
Vol. 15, no. 19
p. 6862

Abstract

Read online

Experimental and computer investigations were conducted into long-duration impulse current distribution in the lightning protection system, supplying network, and electrical installation of a test house that was equipped with household appliances. Long-duration impulse currents simulating lightning continuing currents were injected from the unique current generator into the test object. The current distributions in the elements of the test object were measured using current shunts, coaxial cables, and digital oscilloscopes, then they were modeled using the ATP-EMTP software package. The obtained results show a quite good agreement between the measured and computed current waveforms. The relationships between the values of currents at different points of the conductive installation are similar, as reported in previous studies on the fast-changing lightning return stroke component distribution, although the efficiency of the lightning protection system (LPS) is a few percent better for the long continuing current component in the case of a strongly conductive ground at the test site in Huta Poręby, part of the Rzeszów University of Technology. Due to the relatively low content of high-frequency components in the long continuing current spectrum, the waveshape of this lightning component is practically the same throughout the entire tested installation.