Energies (Nov 2019)

DC Side Bus Voltage Control of Wind Power Grid-Connected Inverter Based on Second-Order Linear Active Disturbance Rejection Control

  • Youjie Ma,
  • Faqing Zhao,
  • Xuesong Zhou,
  • Mao Liu,
  • Bao Yang

DOI
https://doi.org/10.3390/en12224274
Journal volume & issue
Vol. 12, no. 22
p. 4274

Abstract

Read online

In order to improve the dynamic response speed and the steady-state performance of the DC side bus voltage of the wind power grid-connected inverter, a mathematical model of a typical three-phase voltage type PWM (Pulse Width Modulation, PWM) grid-connected inverter was established, and its traditional voltage-current double closed loop with proportional-integral control method was analyzed. Then a second-order linear active disturbance rejection controller that does not depend on system model information was designed to replace the traditional voltage outer loop proportional-integral controller, thus a new double closed-loop control structure was formed to control it. The frequency domain theory was used to analyze the convergence of the third-order linear extended state observer and the influence of the total disturbance on the performance of the third-order linear extended state observer. The parameter tuning scheme of the designed controller was given. Finally, the 1.5 MW direct-driven permanent magnet wind power generation system was built in the Matlab/Simulink software and the control effects of the two control modes under different working conditions are compared. The simulation results show that the control scheme designed in this paper is superior to the traditional proportional-integral controller which has good anti-interference characteristics and robustness. Especially it has a good stability effect on DC side bus voltage fluctuations.

Keywords