Bulletin of the Polish Academy of Sciences: Technical Sciences (Apr 2021)

IEC 61850 interface for real time power system simulation

  • Karol Kurek,
  • Łukasz Nogal,
  • Ryszard Kowalik,
  • Marcin Januszewski

DOI
https://doi.org/10.24425/bpasts.2021.137057
Journal volume & issue
Vol. 69, no. 3

Abstract

Read online

Real time simulators of IEC 61850 compliant protection devices can be implemented without their analogue part, reducing costs and increasing versatility. Implementation of Sampled Values (SV) and GOOSE interfaces to Matlab/Simulink allows for interaction with protection relays in closed loop during power system simulation. Properly configured and synchronized Linux system with Real Time (RT) patch, can be used as a low latency run time environment for Matlab/Simulink generated model. The number of overruns during model execution using proposed SV and GOOSE interfaces with 50 µs step size is minimal. The paper discusses the implementation details and time synchronization methods of IEC 61850 real time simulator implemented in Matlab/Simulink that is built on top of run time environment shown in authors preliminary works and is the further development of them. Correct operation of the proposed solution is evaluated during the hardware-in-the-loop testing of ABB REL670 relay.

Keywords