IEEE Access (Jan 2019)

Measurement and Analysis of PMU Reporting Latency for Smart Grid Protection and Control Applications

  • Steven M. Blair,
  • Mazheruddin H. Syed,
  • Andrew J. Roscoe,
  • Graeme M. Burt,
  • Jean-Pierre Braun

DOI
https://doi.org/10.1109/ACCESS.2019.2903929
Journal volume & issue
Vol. 7
pp. 48689 – 48698

Abstract

Read online

Emerging power system protection and control applications require faster-responding measurements and more accurate knowledge of the actual latency of the measurement and communications systems. A new method for accurately determining the reporting latency of a phasor measurement unit (PMU) has been developed and demonstrated. This method operates in real-time, works passively for any existing PMU without requiring changes to the PMU hardware or software, and it is very accurate-providing a measurement uncertainty of <;500 ns in many cases, significantly surpassing the 0.002 s accuracy requirement in the most recent IEEE Synchrophasor standard. Only low-cost hardware and open source software are required. It is particularly important to understand end-to-end system latency, including the impact of local and wide-area communications, rather than just the latency of the PMU device; the proposed method also supports such practical measurements. It is therefore shown how this advance can be used to enable efficient, but realistic, cross-domain power system simulation studies, which incorporate measurement and communications delays. These capabilities address complexity and uncertainty in the design and operation of future PMU-based protection and control functions for new smart grid services.

Keywords