Applied Sciences (Jun 2024)

The Intersection of Architectural Conservation and Energy Efficiency: A Case Study of Romanian Heritage Buildings

  • Simona Elena Șerban,
  • Tiberiu Catalina,
  • Razvan Popescu,
  • Lelia Popescu

DOI
https://doi.org/10.3390/app14114835
Journal volume & issue
Vol. 14, no. 11
p. 4835

Abstract

Read online

In Europe, it is estimated that 14% of existing buildings were built before 1919, whereas 26% were built before 1945. In Romania, about 31% of the buildings date from before 1961, contributing to the current stock of old buildings with historic and architectural value in the country. This paper illustrates the current state of buildings with historic and architectural value in Romania, alongside a case study of a representative administrative building in Câmpulung, Romania. The analysis of the Town Hall building in Câmpulung, Romania, demonstrates that potential energy savings of up to 47.53% can be achieved by implementing interventions such as upgrading windows, insulating the attic, and installing photovoltaic panels. The highest energy reduction is obtained by replacing the window glass with a value of 18.16% with attic insulation with a value of 16.1%. This paper also presents indoor measurements of temperature and humidity in different offices positioned in the north and the south. The study conducted on the south façade office revealed consistent temperatures ranging from 21.7 °C to 24.4 °C, with an average of 23.31 °C. However, the humidity levels fluctuated considerably, ranging from 17.1% to 39.1%, with an average of 26.89%. The sun-exposed section of the building saw relatively stable temperature conditions, but the varying humidity levels could have a detrimental impact on the quality of the indoor atmosphere and potentially decrease the effectiveness of the workforce. By contrast, the north façade office exhibited lower and more fluctuating temperatures, ranging from 19.8 °C to 23.6 °C, with an average of 21.74 °C. Additionally, it had higher and more stable humidity levels, ranging between 19.5% and 41.7%, with an average of 29.83%. A thermographic analysis was performed on the north façade of the Câmpulung Town Hall, utilizing thermal imaging technology to detect areas of heat loss, and thus identifying the energy inefficiency problems of the building’s exterior. The investigation found notable variations in temperature, especially around the windows, where temperatures could be as high as 14.1 °C, highlighting the insufficiency of the building’s antiquated timber-framed windows in preventing energy loss.

Keywords