Energies (May 2024)

Experimental Study of the Behaviour of Ring Main Unit-Type Panels in the Event of Internal Arcing in Different Compartments

  • Cristian-Eugeniu Sălceanu,
  • Sorin Enache,
  • Cătălin Dobrea,
  • Daniela Iovan,
  • Daniel Ocoleanu,
  • Marcel Nicola,
  • Ștefan Șeitan,
  • Mihai Ionescu

DOI
https://doi.org/10.3390/en17112500
Journal volume & issue
Vol. 17, no. 11
p. 2500

Abstract

Read online

If an R.M.U. (Ring Main Unit) cubicle is installed, operated and maintained in accordance with current standards and the manufacturer’s instructions, the likelihood of internal arcing is reduced, but should not be completely ignored. This article outlines the experimental situations in which arcing can occur and the catastrophic effects seen if R.M.U. is not properly designed for this type of damage. This type of failure can be caused by a fault, abnormal operating conditions or a malfunction and represents a danger during its installation and to persons present. The situations in which this type of failure can occur are presented and experimentally analysed: bi-phase internal arcing in the connections compartment, three-phase internal arcing in the switching compartment, internal arcing in the fuse compartment and single-phase arcing between a phase and the switchgear enclosure.