Energies (Apr 2023)

Simulation and Experimental Study on the Use of Ventilation Air for Space Heating of a Room in a Low-Energy Building

  • Piotr Michalak

DOI
https://doi.org/10.3390/en16083456
Journal volume & issue
Vol. 16, no. 8
p. 3456

Abstract

Read online

In thermally modernised buildings, sharing of ventilation heat loss becomes more significant. In the case of the application of ventilation with heat recovery, especially during transitional periods, there arises a question of whether an air system makes it possible to maintain the required indoor air temperature without the necessity of using a basic hydronic heating system. This paper presents the application of a simple thermal network model of a building zone to simulate indoor air temperature in a single room of a multi-storey building with a mechanical ventilation system with heat recovery. Ventilation air was supposed to be the only heat source and its ability to maintain the required indoor air temperature was checked in simulations and then compared with measurements. The 5R1C thermal network model of a building zone was used for simulations. Comparison with measurements showed the Mean Absolute Error (MAE) and Root Mean Square Error (RMSE) of indoor air calculation to be 2.37 °C and 2.45 °C, respectively. When including heat flux from the bottom storey through the floor, MAE = 1.28 °C and RMSE = 1.38 °C were obtained.