Problems of the Regional Energetics (Dec 2015)

Research of the Temperature and Humidity Processes in the Air Conditioning Apparatus Varying Air Ion Concentration

  • Marchenko V. G.

Journal volume & issue
Vol. 2015-3, no. 3(29)
pp. 86 – 91

Abstract

Read online

To create comfortable conveniences for people in the room, we have to process the indoor air in the AC apparatus. Depending on given air parameters in the room, the air processing comprises the next steps: heating, cooling, wetting, drying. Except the compliance of the temperature and humidity parameters of air, we must control its ionic composition. Thereby, the experimental analysis of the air preparing in the AC apparatus is given in this article. Thank to that analysis, we can estimate the ionic and deionic impact on the air space in the specific processes of the air preparing. According to the results of experiments, we have identified, that the air temperature varying does not have significant effect on the ionic concentration. The ionic increasing after electric heater is not associated with air temperature. It is the consequence of the electron extrication from the surface of the heating element. Reducing ion moving the high air humidity decreases the concentration of the lightweight ions. The increasing of the ions in the spray-type air washers is explained by ballo-electric effect of spraying water drops, but not the air humidity rising.

Keywords