The Journal of Engineering (Oct 2018)

Fault case analysis and simulation research of neutral-bus arresters multi-column parallel connected in converter station

  • Dianlang Wang,
  • Guogen Li,
  • Long Jiang,
  • Xiaowei Yang,
  • Tianman Pi,
  • Zhongkang Huang,
  • Dong Li,
  • Jie Zhang,
  • Xiangyu Yaoi,
  • Rongyu Su,
  • Lihui Zhang

DOI
https://doi.org/10.1049/joe.2018.8725

Abstract

Read online

High-voltage DC arrester is one of the key equipment for overvoltage protection of ultra-high voltage DC (UHVDC) transmission system. This device plays a decisive role in the insulation level of the whole process. The current distribution between resistance pieces of multi-column parallel arresters is non-uniform, which affects the overall energy absorption capacity of arresters. First, a real failure case of ±500 kV Xiluodu-Nuozhadu HVDC project is introduced. Then, the analysis of the specific failure case is proposed. Finally, a corresponding model is built on PSCAD/EMTDC to study the current distribution characteristics.