Energies (Feb 2021)

DC Current Limiting Characteristics of Flux-Coupled Type SFCL Using Superconducting Element Connected in Parallel in a DC System

  • Young-Pil Kim,
  • Seok-Cheol Ko

DOI
https://doi.org/10.3390/en14041096
Journal volume & issue
Vol. 14, no. 4
p. 1096

Abstract

Read online

In this paper, the fault current limiting (FCL) characteristics of a flux-coupled type superconducting fault current limiter (SFCL) with parallel connection between two windings in a DC system were analyzed. The flux-coupled type SFCL was composed of two coils connected in parallel and a superconducting element (SE), which was connected in series with the secondary coil. The flux-coupled type SFCL works in DC systems similar to those in AC systems. Before a fault occurs, the respective magnetic fluxes generated by the two coils connected in parallel offset each other, maintaining the voltage induced in the two coils at zero. In case of a fault, however, resistance is generated in the SE, preventing the magnetic fluxes generated by the two coils from offsetting each other. Thus, some voltage is induced in the two coils, and this starts to limit the fault current. DC short circuit tests were conducted, and the test results confirmed that the flux-coupled type SFCL with the two parallel connected coils was effective in limiting the fault current in a DC system. Additionally, the effect of the wiring direction of the two coils on the SFCL’s FCL performance and operating current, limiting impedance, and instantaneous power load was further analyzed, and as a result, the performance conditions of the SFCL in a DC system were determined.