Energies (Feb 2023)
On-Line Monitoring of Shunt Capacitor Bank Based on Relay Protection Device
Abstract
In modern power systems, the installation of a shunt capacitor bank is one of the cheapest and most widely used methods for improving the voltage profile. One shunt capacitor bank is composed of mass capacitor units and have ground, ungrounded, delta, wye connections that make configuration of capacitor banks is various. In the case of long-term operation, the failure of a single capacitor unit of a capacitor bank is likely to cause uneven voltage, which will lead to the breakdown and burning of the whole group, resulting in huge losses. The relay protection device can detect the simultaneous voltage and current of the capacitor. By utilizing these data from the relay, the abnormal state of the shunt capacitor banks at the initial stage of the fault can be found through monitoring the slight change in capacitance. Timely and early maintenance and repair would avoid capacitor bank faults and potentially greater economic losses. Capacitor banks have different connection modes. For ungrounded wye-connected capacitor banks with an unknown neutral point voltage, the capacitance parameters of each branch cannot be calculated. A parameter symmetry based on the calculation method for capacitor parameters is proposed. For long-term monitoring and observation of the capacitor capacitance value, the fault state and abnormal state of the capacitor are identified based on statistical methods. The simulation established by PSCAD verified that a relay protection device can realized an effective monitoring of the early abnormal state of the capacitor bank.