Energies (Sep 2022)

Comparison between the PD Characteristics of g<sup>3</sup> and Dry Air for Gas-Insulated Switchgears

  • Goang-Chul Shin,
  • Sung-Wook Kim,
  • Gyung-Suk Kil

DOI
https://doi.org/10.3390/en15197043
Journal volume & issue
Vol. 15, no. 19
p. 7043

Abstract

Read online

This paper presents a comparison between the partial discharge (PD) characteristics of g3 and dry air for gas-insulated switchgears. PD signals were measured with a conventional method according to IEC 60270 and an ultra-high frequency (UHF) method. The partial discharge inception voltages (PDIVs) of g3 and dry air are about 74% to 84% and 58% to 72%, respectively, in the protrusion on conductor (POC) system, and 90% to 96% and 80% to 93%, respectively, in the free moving particle (FMP) system, depending on the gas pressure of 0.1 MPa to 0.5 MPa. The single PD pulse in time and frequency domains are not distinguished according to gas type. The PRPD patterns have different phase angles depending on the gas type in the POC, while the phase angle is 0–360° in the FMP, regardless of the gas type. Lastly, the correlation was analyzed, showing that the output voltage in mV of the UHF sensor increases linearly in accordance with the apparent discharge in pC, regardless of the gas type. The experimental results in this paper are important as a fundamental database for the application of UHF monitoring systems in an eco-friendly GIS.