Global Energy Interconnection (Feb 2019)

Distance protection of EHV long transmission lines considering compensation degree of shunt reactor

  • Wang Jiang,
  • Jiping Lu,
  • Hongji Xiang,
  • Xing Ma,
  • Hui Fang

Journal volume & issue
Vol. 2, no. 1
pp. 64 – 70

Abstract

Read online

This study investigated the feasibility of distance protection in extra-high voltage (EHV) networks. In long-distance transmission lines, the distributed parameter characteristic of the EHV network is obvious. When a fault occurs far away from the measurement site, the measured impedance might not be directly proportional to the fault distance, and the protection domain of distance protection will be decreased. The detailed theory inferred and proven in this paper reveals that this phenomenon is widespread in EHV transmission lines. The results indicate that the protection domain error is greatly reduced by the application of the shunt reactor. Overall, simulation results show that the proposed method is effective for impedance relay, considering different characteristics, different lengths of lines, and compensation degrees. Keywords: EHV, Distance protection, Shunt reactor, Compensation degree