E3S Web of Conferences (Jan 2019)

Experimental Comparison of Radiant Ceiling Panels and Ceiling Panels Containing Phase Change material (PCM)

  • Bogatu Dragos-Ioan,
  • Bourdakis Eleftherios,
  • Kazanci Ongun Berk,
  • Olesen Bjarne W.

DOI
https://doi.org/10.1051/e3sconf/201911101072
Journal volume & issue
Vol. 111
p. 01072

Abstract

Read online

Two commercially available ceiling panels, one metal and one gypsum incorporating microencapsulated PCM were compared experimentally to determine their limitations and ability to provide an adequate indoor thermal environment. The experiments took place from February to May 2018 in a climate chamber at the Technical university of Denmark. In total, seven scenarios were evaluated, five with active cooling, where the flow rate and solar heat gains were varied, and two without. Results showed that according to EN 15251:2007, the RCPs maintained the best indoor thermal environment for 91% of occupancy time in Category III – operative temperature between 22oC and 27oC, and 75% in Category II – operative temperature between 23oC and 26oC, for a 140 kg/h flow rate and the reference solar heat gains. Alternatively, the PCM panels maintained Category III for only 48% of the time, while only 30% in Category II for a 220 kg/h flow rate and the reference solar heat gains. The PCM panel presented the ability to store the heat for a later time. However, the PCM panels’ solution proved inadequate in terms of heat storage capacity, pipe positioning and thermal conductivity while improvements are required in order to employ them in new and renovated buildings.