Resources (May 2021)

Enhancement of a District Heating Substation as Part of a Low-Investment Optimization Strategy for District Heating Systems

  • Anna Vannahme,
  • Mathias Ehrenwirth,
  • Tobias Schrag

DOI
https://doi.org/10.3390/resources10050053
Journal volume & issue
Vol. 10, no. 5
p. 53

Abstract

Read online

In an ongoing project, low-investment measures for the optimization of district heating systems are analyzed. The optimization strategies are collected in a catalog, which is the core of a guideline. The application of this guideline is demonstrated using two concrete district heating networks as examples. In this study, the improvement of an analog controlled district heating substation by an electronic controller is investigated. High supply temperatures and heat losses are often a challenge in district heating networks. The district heating substations have a major influence on the network return temperatures. The comparison of the two substation setups with analog and electronic controllers is carried out by laboratory measurement. It can be shown that the return temperatures can be reduced by an average of 20 K in winter and transition, as well as 16 K in summer. The district heating network losses are calculated for one of both specific district heating networks. They are calculated from the ratio of network losses to generated energy. The generated energy is the sum of network losses and consumer demand. The thermal losses of the network can be reduced by 3%. The volume flow in the heating network can be reduced to a quarter. Therefore, the pumping energy requirement drops sharply since these changes cubically affect the volume flow.