Applied Sciences (Apr 2018)

Diagnostics of Hydrogen-Containing Mixture Compression by a Two-Stage Piston Compressor with Cooling Demand Prediction

  • Tomáš Brestovič,
  • Mária Čarnogurská,
  • Miroslav Příhoda,
  • Peter Lukáč,
  • Marián Lázár,
  • Natália Jasminská,
  • Romana Dobáková

DOI
https://doi.org/10.3390/app8040625
Journal volume & issue
Vol. 8, no. 4
p. 625

Abstract

Read online

The present article describes the diagnostics of a compressor that is compressing a mixture of H2 and N2 on the basis of the results that were obtained by operational measurements of the flow rates and temperatures at selected compressor sites, as well as of the acoustic pressure levels during the full loading thereof. The obtained data were subsequently used to determine the limit conditions of the compressor operations in terms of the cooling capacity. A thermodynamic analysis of the compression of the H2/N2 gas mixture was carried out with subsequent heat and energy flow calculation and the determination of the minimum cooling water flow rate that is required to ensure the continuous compressor operations.