发电技术 (Jun 2024)

Research and Application of Deep Peak Shaving of 350 MW Supercritical Fluidized Bed Unit

  • DAI Huasong,
  • PU Shaoxu,
  • CHAI Guoxu,
  • JIN Li,
  • CHEN Weiping,
  • XIE Mingliang

DOI
https://doi.org/10.12096/j.2096-4528.pgt.22134
Journal volume & issue
Vol. 45, no. 3
pp. 401 – 411

Abstract

Read online

ObjectivesIn order to master the deep peak shaving capability of supercritical circulating fluidized bed units and scientifically participate in the auxiliary service market, it is necessary to conduct in-depth research on the deep peak shaving performance of existing units.MethodsFrom the three dimensions of safety, economy and environmental protection, 40% and 30% of rated load continuous trial operation, boiler combustion optimization adjustment, boiler efficiency and steam turbine heat consumption rate performance tests were carried out, respectively.More than 10 optimization measures such as single pump operation of feed water pump, pressure curve optimization, boiler oxygen amount, bed pressure adjustment, etc., were implemented.ResultsThe continuous operation of 30% rated load for 12 consecutive days was realized, 40% and 30% rated load depth peak-monasizing the peaks affected coal consumption by about 52%, 72 g/(kW·h), respectively.ConclusionsThe 350 MW supercritical circulating fluidized bed unit has good deep peak shaving ability. There is no need to transform 30% rated load conditions, and inject oil to stabilize combustion and maintain high efficiency of the boiler. Monitoring parameters for the steam turbine generator unit body, thermal system and auxiliary equipment are normal. The main flue gas pollutants are ultra-low emission.