Energies (Apr 2022)

The Performance Analysis of an Integrated CO<sub>2</sub> Refrigeration System with Multi-Ejectors Installed in a Supermarket

  • Engin Söylemez,
  • Armin Hafner,
  • Christian Schlemminger,
  • Ekaterini E. Kriezi,
  • Vahid Khorshidi

DOI
https://doi.org/10.3390/en15093142
Journal volume & issue
Vol. 15, no. 9
p. 3142

Abstract

Read online

The field data from an integrated CO2 refrigeration system installed in a supermarket located north of the capital of Lisbon was analyzed. The goal was to demonstrate the effect and performance of multi-ejectors on a refrigeration system operating in a warm climate. The measurement results for the system with and without activating ejectors were compared. It was observed that the system with a multi-ejector operation had considerable performance superiority. The ejectors improved the cooling capacity of the medium temperature stage of the system by 17.4%. The system with active ejectors had 7.5% less total power consumption compared to the ejector off mode of the same system.