Heliyon (Sep 2024)
Investigation of distribution system modification using operation voltage unification in order to decrease interruptions in dust climate
Abstract
Many events in power networks which caused failure and outage of subsystems have root in design and initial selection of equipment and their specification. This concern will be important while the any kind of expanding and acclimation plan need to be executed to strengthen the existing infrastructures in order to provide better condition with regard to satisfied criteria. In Iran one of the most adverse environmental occurrences known Fine Dust, may force several distribution utilities to be changed due to new technical requirements. Medium voltage level regrading in way to decrease or unification of distribution system have been proposed in this paper to reach reduced faults and fast replacement of equipment in damaged situations. Voltage level changing and selection have been investigated in order to increase the network strengthen and reselection of equipment and redesigning critical sections of system against natural events that called fine dust with aim to attain an upgraded distribution utility. Operating of existing 33 kV and 11 kV network in 20 kV level and investigation of changing process have been done for Ahvaz medium voltage distribution system as a case study in these paper's sections. Calculations and results will be contained maximum current capacities in different line conductors, insulation and air clearances assessment, poles acceptable mechanical values, short circuit current and protection coordination for changing voltage level in distribution system.