Energies (Sep 2024)

A Single-Phase Ground Fault Line Selection Method in Active Distribution Networks Based on Transformer Grounding Mode Modification

  • Shi Su,
  • Qingyang Xie,
  • Pengfei Ma,
  • Yuan Li,
  • Fahui Chen,
  • Jing Zhang,
  • Botong Li,
  • Changqi Wang

DOI
https://doi.org/10.3390/en17184743
Journal volume & issue
Vol. 17, no. 18
p. 4743

Abstract

Read online

Reliable fault line selection technology is crucial for preventing fault range expansion and ensuring the reliable operation of distribution networks. Modern distribution systems with neutral earthing via arc extinguishing coil face challenges during single-phase ground faults due to indistinct fault characteristics and system sequence networks influenced by the grounding methods on the distributed generation side. These factors increase the difficulty of fault line selection. By analyzing the differences between the zero-sequence currents of feeder lines and neutral lines in active distribution networks with neutral earthing via arc extinguishing coil, a method for single-phase ground fault line selection has been proposed in this paper. This method involves switching from a neutral point ungrounded mode to a low-resistance neutral grounding mode using distributed generation grid-connected transformers under permanent fault conditions. Criteria based on the differences in zero-sequence current ratios before and after the grounding mode switch are established. Simulation validation using the Power Systems Computer Aided Design (PSCAD) platform has been conducted. The proposed method demonstrates strong tolerance to transition resistance, simple extraction of fault characteristic signals, and accurate fault line selection results.

Keywords