Energies (Jul 2017)

Design and Implementation of a STATCOM Based on a Multilevel FHB Converter with Delta-Connected Configuration for Unbalanced Load Compensation

  • Wei-Neng Chang,
  • Ching-Huan Liao

DOI
https://doi.org/10.3390/en10070921
Journal volume & issue
Vol. 10, no. 7
p. 921

Abstract

Read online

A delta-connected STATCOM with cascade multilevel full H-bridge (FHB) converter has been applied for phase balancing and power factor correction of unbalanced load in a three-phase, three-wire power distribution system. In this paper, a feedforward compensation formula is presented for the STATCOM by using the symmetrical components method to compensate unbalanced load. Computer simulation is performed for preliminary verification. Accordingly, a hardware prototype employing a TMS320F2812 DSP-based system is built for final verification test. Experimental results show that the proposed STATCOM is very effective for real-time unbalanced load compensation.

Keywords