Energies (Feb 2020)

Earth-Cooling Air Tunnels for Thermal Power Plants: Initial Design by CFD Modelling

  • Eduardo de la Rocha Camba,
  • Fontina Petrakopoulou

DOI
https://doi.org/10.3390/en13040797
Journal volume & issue
Vol. 13, no. 4
p. 797

Abstract

Read online

Climate change and the increase of the consumption of energy resources are expected to further strain anticipated water stress scenarios. The operation of existing thermal plants depends greatly on their cooling capacity, for which large amounts of water are withdrawn and consumed. Dry-cooling systems, on the other hand, do not require water, but they are less efficient and more expensive relative to conventional water-based systems, because of their dependency on the ambient temperature. This paper introduces the new idea of replacing water-based cooling systems in thermal power plants with earth-cooling air tunnels. Based on the concept of existing earth-air heat exchangers, the system takes advantage of the low and relatively constant underground temperature for cooling ambient air before it is introduced in the air condenser of the plant. In this work, we present an initial design of such an open-loop system for a 20 MW concentrated solar power plant. A sensitivity study of both geometric and flow parameters is realized using computational fluid dynamics simulations. Under the requirements of the study, we find that a system using a design of pipes with 0.5 m diameter and about 300 m length can be considered a technically viable zero-water alternative to water-cooling technologies.

Keywords