Energies (Jan 2021)
Thermal Efficiency of Trombe Wall in the South Facade of a Frame Building
Abstract
The article presents the possibility of using a mass collector-storage wall (CSW), integrated into the structure of a building with a light skeleton structure. The considered system is a proposal for an energy-saving solution that can be used in buildings with various utility purposes. The article presents the results of experimental tests of a collector-storage wall mounted in the space of the skeleton structure of the southern facade of a building for the period of one year, as well as the results of numerical simulation. In the summer, the influence of the use of heat-insulating roller shutters on limiting overheating of the chamber interior was investigated. The effect of using the roller shutters is a reduction in the average value of the heat flux by about 77%. In the winter, the energy efficiency of the wall was tested. The obtained effect is energy consumption during the heating season at a level comparable to a wall with a traditional structure with a coefficient of U = 0.30 W/(m2K). The results of the numerical tests showed high agreement with the direct results, which provides a basis for the use of such simulations in further research on the search for the optimal structure of a collector-storage wall.
Keywords