Fire (Apr 2024)

Simulation of Damage Caused by Oil Fire in Cable Passage to Tunnel Cable

  • Feng Liu,
  • Jiaqing Zhang,
  • Mengfei Gu,
  • Yushun Liu,
  • Tao Sun,
  • Liangpeng Ye

DOI
https://doi.org/10.3390/fire7040147
Journal volume & issue
Vol. 7, no. 4
p. 147

Abstract

Read online

In order to evaluate the damage to tunnel cables caused by fire caused by leakage of transformer oil into a cable channel, the fire characteristics of different volumes of transformer oil flowing into a cable channel were analyzed by numerical simulation. The results show that when the total leakage of transformer oil is less than or equal to 3 L, the fire will end within 120 s, and when the total leakage is greater than or equal to 5 L, the fire duration will exceed 900 s. When the leakage amount is 1 L, the cable only burns slightly, and when the leakage amount is 3~12 L, the cable burns obviously. The combustion of the cable is mainly concentrated between 15 s and 75 s, and the overall combustion rate of the cable increases first and then decreases. When the total leakage is greater than or equal to 8 L, the damage distance of the middle and lower layer cable is the smallest. When the total leakage is less than or equal to 5 L, the damage distance of the lower layer cable is the smallest, and the damage distance of the lower layer cable, middle and lower layer cable, and middle and upper layer cable is less than half of the length of the cable channel.