Proceedings (Aug 2018)

A Sub-Zonal PMV-Based HVAC and Façade Control System for Curtain Wall Buildings

  • Marco Arnesano,
  • Andrea Calvaresi,
  • Filippo Pietroni,
  • Lorenzo Zampetti,
  • Sara Magnani,
  • Oscar Casadei,
  • Gian Marco Revel

DOI
https://doi.org/10.3390/proceedings2151138
Journal volume & issue
Vol. 2, no. 15
p. 1138

Abstract

Read online

This paper presents an experimental test room in a curtain wall building where an innovative monitoring and control system was implemented and tested. The proposed solution is composed by an IR-based comfort sensor that measures the PMV (Predicted Mean Vote) index for 2 room’s sub-zones and provides the optimal air temperature set-points. The overall control system includes a distributed sensors and actuators network, also embedded into the façade modules, to measure indoor and outdoor parameters and to regulate fan-coils, windows opening and shadings with a sub-zonal approach. Initial results turn out to provide an energy saving of about 20% with an improvement of thermal/visual comfort and IAQ conditions.

Keywords