Energies (Aug 2022)
A π-Phase-Shifted Fiber Bragg Grating Partial Discharge Sensor toward Power Transformers
Abstract
Partial discharge (PD) ultrasonic detection is an early sign of the insolation defects of power transformers. The early diagnosis of PD requires the high sensitivity and reliability of ultrasonic sensing systems. For this purpose, a reformative PD ultrasonic sensing system based on phase-shifted FBG (PS-FBG) was demonstrated. By using PS-FBG as the ultrasonic sensing unit, the ultrasonic sensing system improved the response to the ultrasonic signal and overcame the electromagnetic noise. To compensate for the influence of temperature change on the ultrasonic sensing system, an automatic wavelength scanning demodulating method was carried out. The wavelength spanning strategy was optimized based on the principle of cross-correlation, in order to quicken the spanning. A PD detection test in the transformer oil was conducted, and the result shows that PS-FBG was 17.5 times more sensitive than PZT. Because of the better ultrasonic response, the proposed system was able to achieve the early diagnosis of insolation faults in a power transformer.