Case Studies in Thermal Engineering (Dec 2021)
Application of energy-saving control strategy in air conditioning terminal equipment based on constant temperature difference of chilled water
Abstract
Effectively reducing the energy consumption of central air conditioning systems is an important aspect of building energy efficiency. The energy consumption of terminal equipment accounts for over 25% of that of air conditioning systems. Although the heat and moisture exchange mechanism of the terminal unit has been extensively studied, studies on control strategies for terminal unit operation are lacking. This study proposes an energy-saving optimization control strategy for terminal units based on the constant temperature difference of chilled water in an engineering application study. A fan coil unit (FCU) controller was designed and manufactured, and a Local Area Network (LAN) control system was constructed and compared to determine the optimal control strategy. When adopting the energy-saving optimization control strategy for the terminal unit based on a constant chilled water temperature difference, the energy consumption of the terminal equipment was significantly decreased by 7.2%. The flow rate of chilled water was reduced by 26.94% when the indoor air temperature requirements were met, effectively reducing the energy consumption of the central air-conditioning system. The adjustment time required to reach a stable indoor temperature was reduced and environmental comfort was improved. These results demonstrate the potential of this control strategy for use in engineering practices to replace traditional control modes.