Analysis of Harmonic Instability of Tokamak Power System Caused by Rectifier Transformer Bias

  • Jiansheng WANG,
  • Huafeng MAO,
  • Zhiwei MAO,
  • Liuwei XU

DOI
https://doi.org/10.16516/j.gedi.issn2095-8676.2022.02.009
Journal volume & issue
Vol. 9, no. 2
pp. 70 – 76

Abstract

Read online

[Introduction] The paper aims to effectively suppress the disturbance of non characteristic harmonics to the power grid in the tokamak power supply system, the paper studies the mechanism of low-frequency harmonics in the tokamak power supply system. [Method] By introducing an improved switching function model, selected ITER fusion device as an example and established its corresponding AC/DC equivalent circuit model combined with its corresponding parameters, the corresponding output second harmonic was obtained through calculation and simulation. [Result] The ratio of output to input is calculated, and the stability factor value almost tends to zero. [Conclusion] It is determined that the DC bias of rectifier transformer do not cause harmonic instability of the system.