Journal of Asian Architecture and Building Engineering (Jun 2024)

Field experiment examining condensation reduction methods based on underground parking lot types

  • Hye Yeon Kim,
  • Min Hee Chung,
  • Jin Chul Park

DOI
https://doi.org/10.1080/13467581.2024.2357756
Journal volume & issue
Vol. 0, no. 0
pp. 1 – 18

Abstract

Read online

In this study, condensation reduction methods with high field applicability to various types of underground parking lots in apartment buildings were selected and tested. The selected methods included floor-insulating drainage plates, induction fans with heating wires, and an automatic control ventilation system based on indoor and outdoor temperatures and humidity. The effectiveness of these methods was evaluated via real-world field experiments. The results indicated that while the insulating drainage plates initially blocked the cold, their long-term effectiveness matched that of normal drainage plates (difference 0.1°C). The induction fan with a heating wire showed average increases of 0.8°C and 2.7°C in wall surface temperature after one and three months, compared to normal induction fans. The absolute humidity of the automatic control ventilation decreased by 1.8 g/kg after 10 h of operation during rainy weather, whereas the manual control ventilation system increased by 0.6 g/kg under the same conditions. This study offers insights into the most effective application of these methods for various parking lot configurations.

Keywords